Electrical Conduit
 
 
 
 
 
Vac Formed V.F.C.
 
   
Go back 1
Download Brochure
Home Electrical Conduits Metallic Tubing Plastic Tubing Fittings Whitehouse Services Contacts & Enquiries
 
VFC Electrical Conduit
 

Typical Applications
VFC conduit is extremely versatile. It can be used in most commercial and industrial environments, where dynamic and static applications are required.
The PVC coating provides a degree of weatherproofing & protection to IP65 (tubing only) or IP54 (with fittings attached).
Low  Smoke & Fume (LSF) PVC coating make it ideal for use in areas where fire is a particular concern
Construction
VFC is made from electro galvanised steel strip, which is helically wound to produce a square lock construction. Made to BS731. It is then vacuum coated with a uniform thickness of LSF (low smoke and fume) flexible PVC. The standard colour is black but other colours are available to order......... ....... Max Operating Temp: -25 to +70 'C
IP Rating: (tube) IP65 (tube + fittings) IP54

 
 
Bore Size
Inside Diameter
(mm)
Outside Diameter
(mm)
Inside Bent Radius
(mm)
Kg per 100 metres
 

VFC.6

5
8.5
26
8

VFC.10

7
10
27
11

VFC.12

9.3
13.2
28
18

VFC.16

13.1
17
33
25

VFC.20

16.4
20.6
41
31

VFC.25

19.3
24
45
36

VFC.32

25.8
31.8
60
54

VFC.40

32
38
75
66

VFC.50

38
44.5
93
77

VFC.63

50
56
125
112